A new era in data communication ...Introducing the world’s first integrated, interactive data logging and alarm notification system
Finally …one flexible system is all you need for all your data and event logging, alarm notification, and status checking needs. RACO’s Catalyst® Interactive Communications System provides an up-to-the-minute, two-way connection with your critical data-whether through traditional phone, pager, cell phone, or fax channels.
N/AModbus RTU Master protocol via RS-232, RS-422, RS-485
# of Phone Numbers Dialed
N/A96
Speech Messages
N/AUsers record their own messages. Also includes resident vocabulary for programming guidance and for default "alarm/normal" speech if no user messages are recorded.
UL Standard
N/ACatalyst® complies with UL Standards: 1459, 1950
Communication Method
N/ALandline Wireless - Cellularm
Notification Methods
N/AFax PA System Pager Voice Call
Standard Features
Total Channels
N/Aup to 56 points monitored including channels interfaced via Modbus, and four internal universal (analog/digital) inputs
User Memory
N/A1 MB standard (Optional: Up to 5 MB of memory for user speech and data log file)
Internal Log File
N/ACollects periodically sampled channel data, alarms, state and configuration changes. Log file transfers to faxes, data collection stations, and RACO Alarmware
Destination Types
N/ATraditional voice phone, numeric and alphanumeric pagers, faxes, e-mail, data log collection stations, RACO Central Station, and PA Systems
Channel Grouping
N/AMay assign channels to different destination groups for responsible personnel targeted calling
Voice Messages
N/AUp to 478 seconds of voice messages
Configuring
N/AProgrammed via front panel, remote telephone or Alarmware Software
RACO Alarmware Software
N/ALocally or remotely configures units, collects log files and maintains configurations for multiple units
Firmware Upgrades
N/AUse Alarmware to upgrade unit without changing hardware or returning unit to factory
Battery Backup Time
N/A10 hours
Warranty
N/A5 years
Data Logging
Frequency Interval
N/A10 sec - 24 hr
# of Samples
N/AUp to 740000
# of Channels
N/AUp to 256
Connectivity
Modbus Port
N/ARS232 9 pin D Sub male RS485 9 pin D Sub male
Alarmware Programming Port
N/ARS232C 9 pin D Sub male
Serial Printer Port
N/ARJ45 modular connector
Electrical
Universal Input Sensing
N/ADigital: unpowered contact inputs, open contacts see 5 volts DC; closed see 10mA DC Analog: 4-20mA current loop, scalable in engineering units, resolution: 0.1%, accuracy: 10 bits
Power Requirements
N/A105-135 VAC, 50/60 Hz, 15 watts maximum or 8-14 VDC at 500 mA maximum
Power Consumption
N/AStandby 420 mA, active 450 mA
Battery Charging
N/APrecision voltage controlled, including automatic rapid recharge after drain.
Surge Protection
N/AIntegral gas tube and solid-state protectors on all phone, power, and signal lines.
Physical
Indoor Enclosure
N/ANEMA 1 - Rugged Metal
Weight
N/A8 lbs3.6 kg
Height
N/A11 7/8 in.
Width
N/A9 in.
Depth
N/A5 in.
Mounting Centers
N/A11 3/8" vertical x 6" horizontal
Environmental
Temperature Range
N/A20 to 130 ºF
Humidity
N/A0 to 95%, Non-condensing
Telephone
N/ADialing Methods: Selectable TouchTone or pulse dialing Total Destinations: Up to 96 different numbers; each up to 255 digits long Destination Types: Traditional voice phone, numeric and alphanumeric pagers, faxes, e-mail, data log collection stations, RACO Central Station, and PA Systems Alarm Acknowledgement: TouchTone key, by calling back, or Alarmware Speakerphone: Built-in for two-way on-site calling PBX Delays: Programmable in increments of 1 second Compatibility: Compatible with most cellular telephone systems FCC Registration: Part 68, "Ringer Equivalence": 0.3A
Accessories
N/A4 MB Memory: 4 MB Memory upgrade for the following models: C10-S-020-1450 and C1S-S-020-1450 NEMA 4X Enclosure : Fiberglass NEMA 4X enclosure, water tight/dust tight with locking HASP Serial Printer Cable: 6' Catalyst® to serial printer cable Modbus Cable: 6' Catalyst® to Modbus cable Alarmware Cable: 6' Catalyst® to computer cable Cellularm: Cellularm cellular telephone communications system for the Catalyst®. Includes cellular telephone, 12 hour standby battery, "Rubber Ducky" antenna, and a NEMA 4X enclosure that houses all the above components Power Supply: UL approved, CSA/UL approved Environmental: Heater with thermostat control
Data Logging with Immediate Access
N/ANow you can perform data logging and get an immediate report-without going to the site.
RACO's Catalyst® monitors up to 256 points to provide extensive data and event logging capabilities. Featuring up to five megabytes of on-board memory, the system can monitor data samples, alarms, channel state changes, and configuration changes. At any time, you can obtain the status of level and temperature indicators, flow meters, switches, annunciator panels, motors, pumps, compressors, PLCs, SCADA systems, and other devices.
Constant Communication Using Any Source
N/ADownload a status report today…be alerted of alarm conditions…change a parameter…any time, using virtually any communications source. With Catalyst®, you're always in touch-via phone, fax, e-mail, voice mail, pager, or cellular networks. For general or keyword- selectable information, contact Catalyst®. One of your pumps is down. Catalyst® contacts up to 96 user destinations, communicating the alarm location and status in a voice message. Or Catalyst® can report the condition to a central computer.
Versatile Inputs and Interfaces
N/ACatalyst® features 4 standard internal inputs that are easily configured to sense digital or analog signals, and 56 remote channel inputs that are expandable to 256.
The system interfaces with any PLC, or with any other device using Modicon’s Modbus protocol, using only RS232 communications.
Easy Programming and Upgradeability
N/ACatalyst® is easily programmed- even from remote locations-with a free download of RACO Alarmware® This software allows users to quickly set up all monitoring, reporting, and control functions. A PIN-based security system safeguards all settings. Upgrades are simply downloaded and may be accessed from the Internet, so you can get the most current functionality and features without ever having to remove the unit from service.